More info
Description / Abstract:
This document describes time domain reflectometry (TDR) methods for
measuring and calculating the
characteristic impedance, Z(0), of a transmission line on a printed
circuit board (PCB). In TDR, a
signal, usually a step pulse, is injected onto a transmission line and
the Z(0) of the transmission
line is determined from the amplitude of the pulse reflected at the
TDR/transmission line
interface. The incident step and the time delayed reflected step are
superimposed at the point of
measurement to produce a voltage versus time waveform. This waveform
is the TDR waveform and
contains information on the Z(0) of the transmission line connected to
the TDR unit.
Note: The signals used in the TDR system are actually rectangular
pulses but, because the duration
of the TDR waveform is much less than pulse duration, the TDR pulse
appears to be a step.
Applicability
The observed voltage or reflection coefficient change in the TDR
waveform is related to the
difference between Z(0) of the transmission line and the impedance of
the TDR. If the impedance of
the TDR unit is known via proper calibration, then the Z(0) of the
transmission line attached to
the TDR unit may be determined. Thus, the TDR method is useful for
measuring Z(0) and changes in
Z(0) of a transmission line. These impedance values thus determined
can be used to verify
transmission line design (engineering development), measure production
repeatability, and qualify
manufacturers via transfer or artifact standards.
Engineering development requires detailed information on the
electrical performance of prototype
units to assure the transmission line design yields the expected
performance characteristics.
Detailed laboratory analysis of the effect of variations in design
features expected in actual
manufacture can be done to assure the proposed design can be
manufactured at a useful quality
level.
Measurement System Limitations
Measurements of Z(0) often vary greatly, depending on equipment used
and how the tests were
performed. Following a specified method helps assure accurate and
consistent results. Both
single-ended and differential line measurements have limitations in
common, including the
following:
a. The Z(0) measured units are derived and not directly measured.
b. The value of characteristic impedance obtained from TDR
measurements is traceable to a national
metrology institute, such as the National Institute of Standards and
Technology (NIST), through
coaxial air line standards. The characteristic impedance of these
transmission line standards is
calculated from their measured dimensional and material parameters.
c. A variety of methods for TDR measurements each have different
accuracies and repeatabilities.
d. If the nominal impedance of the line(s) being measured is
significantly different from the
nominal impedance of the measurement system (typically 50 Ω), the
accuracy and repeatability
of the measured numerical valued will be degraded. The greater the
difference between the nominal
impedance of the line being measured and 50 Ω, the less reliable
the numerical value of the
measured impedance will be.
e. Measurement variation (repeatability, reproducibility) may only be
a small component of the
total uncertainty in the value of the characteristic impedance. For
example, if the uncertainty in
the characteristic impedance of the reference air line is ± 0.5
Ω (for a 95 %
confidence interval), then the uncertainty in the measured
characteristic impedance of the test
line can be no better than ± 0.5 Ω even if measurement
variation is much less.
f. The particular TDR methods described herein are not suited for
measuring the characteristic
impedance as a function of position along the transmission line
(impedance profiling) because
signal reflections within the transmission line under test and between
the TDR unit and
transmission line under test may adversely affect measurement results.
g. The requirements for the length of the transmission line under test
given in Section 3 of this
test method as well the IPC-2141 must be met.
Further measurement considerations and notes are provided in Section
6.
Sample Limitations
The type of test sample used may also impact Z(0) values (see
IPC-2141). The sample-based
limitations include:
a. The transmission line under test varies along its length whereas
the value of Z(0) obtained
assumes a uniform transmission line. Therefore, the measured Z(0) only
approximates the
characteristic impedance of an ideal line that is representative of
the line under test.
b. Lines on a printed circuit board may deviate significantly from
design. For example, microstrip
lines longer than 15 cm [5.91 in] on boards with plated-through holes
often have variations in line
width; this variation is due to plating and/or etching variations.
c. If the transmission line is too short, the accuracy of the
calculated impedance value may be
degraded (see 4.1.2). If the transmission line is too long, skin
effect and dielectric loss may
cause a bias in the impedance measurement.
d. Depending on where the measurements are made, the value of Z(0)
obtained may be affected by
dielectric and conductor loss and other effects. The farther away from
the interface between the
probe and the transmission line under test, the worse these effects
will be.
e. Duration of the measurement window (waveform epoch) may need to be
adjusted for sample length
and location of midpoint vias along the transmission line.